GV series motor protection circuit breaker are mainly used fo the overload and short circuit protection of the motor in AC 50/60Hz, up to 660V, 0.1-80A power circuit, as a full-voltage starter to start and cut off the motor, under the AC3 load or for the overload and short circuit protection of the circuit and power equipment in the power distribution network.

Specification

Type

Standard power ratings of 3-phase motors 50/60Hz in category AC-3

Current setting range (A)

220V

380V

415V

440V

500V

660V

kW

kW

kW

kW

kW

kW

GV2-M01

-

-

-

-

-

-

0.1-0.16

GV2-M02

-

-

-

-

-

-

0.16-0.25

GV2-M03

-

-

-

-

-

-

0.25-0.4

GV2-M04

-

-

-

-

-

0.37

0.4-0.63

GV2-M05

-

-

-

0.37

0.37

0.55

0.63-1

GV2-M06

-

0.37

-

0.55

0.75

1.1

1-1.6

GV2-M07

0.37

0.75

0.75

1.1

1.1

1.5

1.6-2.5

GV2-M08

0.75

1.5

1.5

1.5

2.2

3

2.5-4

GV2-M10

1.1

2.2

2.2

3

3.7

4

4-6.3

GV2-M14

2.2

4

4

4

5.5

7.5

6-10

GV2-M20

4

7.5

9

9

9

11

13-18

GV2-M21

5.5

11

11

11

11

15

17-23

GV2-M22

5.5

11

11

11

15

18.5

20-25

GV2-M32

7.5

15

15

15

18.5

26

24-32