DAB7 L7 Mini circuit breaker

 
Product Model Pole Trip type Rated current
DAB7-63 1P C 63
1P 2P 3P 4P B:Type B C:Type C D:Type D 1:1A 10:10A 32:32A 2:2A 16:16A 40:40A 3:3A 20:20A 50:50A 4:4A 25:25A 63:63A 6:6A
 

Normal operating conditions and installation conditions

  ■ Ambient air temperature of L7 6/10KA Miniature Circuit Breaker: -5℃~40℃, and average temperature in 24h below +35℃. ■ Altitude of the installation site should not exceed 2000m. ■ Atmospheric relative humidity at ambient air temperature is + 40℃ for not more than 50%, in the low temperature can have higher relative humidity. Consider the temperature changes in product on the surface of the gel and take special measures. ■ Pollution degree: Ⅱ. ■ Installation conditions: installed in a place without significant impact, vibration, no explosion in the medium. ■ Installation: mounted on the TH35-7.5 rail. ■ Installation category: Ⅱ, Ⅲ.

Product Categories

■ According to the poles, L7 is divided into: single pole, two poles, three poles, four poles and other types; ■ According to the instantaneous tripping current form: C type, D type (B type can be customized when required); ■ According to the rated current: 1A, 2A, 3A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 60A, 63A; ■ According to the rated voltage: 110V, 230V (220V), 400V (380V) (230V for single pole, 400V for two poles, three poles and four poles);

Description of trip type of DAB7-63 Miniature Circuit Breaker (6/10KA MCB)

Type B: Suitable to provide line protection for resistive load and low sense power distribution system, and line protection of more electronic circuit, commonly used in electric vehicle protection. Type C: Suitable to provide line protection for inductive load and high sense lighting system, generally referred to as distribution protection. Type D: Suitable to provide line protection for high inductive load and distribution system with a larger impact current, generally referred to as power protection.

Introduction of poles

The number of poles: A. Single-pole circuit breakers; B. Two-pole circuit-breakers with two protective poles; C. Three-pole circuit-breakers with three protective poles; D. Four-pole circuit-breakers with four protective poles.

Technical parameters

Rated short - circuit capacity
Rated current Pole Rated voltage(V) Rated short - circuit current(kA)
1~63A 1P 230/400 6/10kA mcb
1~63A 2P、3P、4P 400 6/10kA mcb
Mechanical And Electrical Life
Category Time Operating frequency(time/h) Rated current(A)
Electrical Life 4000 240 6~32
120 40~63
Mechanical Life 10000 240 6~63
Over-current protection characteristics under the environment temperature of 30 ℃ ~ 35 ℃
No. Rated current (A) Initial state Test current Set time Prosrective result Remark
1 6~63 Cold 1.13In t≤1h Non tripping
2 6~63 Then after the last test 1.45In t≤1h Tripping The current rise steadily to a fixed value within 5S
3 In≤32 Cold 2.55In 1s<t<60s Tripping
In>32 Cold 2.55In 1s<t<120s Tripping
4 6~63 Cold 5In t≤0.1s Non tripping Type C
10In t<0.1s Tripping
10In t≤0.1s Non tripping Type D
20In t<0.1s Tripping
Trip type Rated current A Rated short - circuit breaking capacity A COSΦ
C、D 6≤In≤63 6/10KA mcb 0.45~0.50