| MCB DAB6-100 | |||||||
| For protection of general power distribution (IEC/EN 60898-1) | |||||||
| Poles |
1P |
2P |
3P |
4P |
|||
| Electrical performance | |||||||
| Functions |
short circuit protection,overload protection,isolationg,control |
||||||
| Rated frequency f(Hz) |
50-60Hz |
||||||
| Rated working voltage Ue(V) AC |
230/400 |
400 |
|||||
| Rated current In(A) |
63,80,100,125 |
||||||
| Rated insulated voltage Ui (V) |
500 |
||||||
| Impulse withstand voltage Uimp( kV) |
4 |
||||||
| Instantaneous tripping type | DAB6-100N |
B/C/D |
|||||
| DAB6-100H | B/C/D | ||||||
| Rated short circuit Icn(kA) | DAB6-100N | 6 | |||||
| DAB6-100H | 10 | ||||||
| Release type | Thermal magnetic type | ||||||
| Service life(O~C) | Mechanical | Actual value | 8500 | ||||
| Standard value | 4000 | ||||||
| Electrical | Actual value | 1500 | |||||
| Standard value | 1000 | ||||||
| Connection and installation | |||||||
| Protectiom degree | IP20 | ||||||
| Wire(mm²) | 1~35 | ||||||
| Working temperature | -5~+40℃ | ||||||
| Resistance to humidity and heat | Class 2 | ||||||
| Altitude above sea | ≤2000 | ||||||
| Relative humidity | +20℃ ,≤90% ;+40℃ ,≤50% | ||||||
| Pollution degree | 2 | ||||||
| Installation environment | Avoid obvious shock and vibration | ||||||
| Installation class | ClassⅡ , ClassⅢ | ||||||
| Mounting | DIN35 rail | ||||||
| Dimensions(mm) (WxHxL) | a | 27 | 54 | 81 | 108 | ||
| b | 80 | 80 | 80 | 80 | |||
| c | 73 | 73 | 73 | 73 | |||
| Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | NOte |
| 40±2oC | Cold position | 1.05In(In≤63A) | t≤1h | Non-release | - |
| Cold position | 1.05In (In[63A) | t≤2h | Non-release | - | |
| Carried out immedi-ately after previous test | 1.30In(In≤63A) | t < 1h | Release | Current smoothlyrises to specified value within 5s | |
| 1.30In (In>63A) | t < 2h | Release | |||
| -5~+40oC | Cold position | 8.00In | t≤0.2s | Non-release | - |
| Cold position | 12.00In | t< 0.2s | Non-release | - |
| Rated current(A) | Nominal cross section of wire mm2 |
| 63A | 16 |
| 80A | 25 |
| 100A | 35 |